OUTPUT | ||||
Model |
SC-120-12 |
SC-120-24 |
||
DC Voltage |
13.8V |
13.4V |
27.6V |
26.5V |
Rated Current |
8A |
0.5A |
4A |
0.3A |
Current Range |
0-8A |
0-0.5A |
0-4A |
0-0.3A |
Ripple & Noise |
120mV |
180mV |
||
Voltage Tolerance |
±1% |
±1% |
||
Effi |
81% |
83% |
||
AC input voltage range |
90~264VAC 127~370VDC |
|||
AC inrush current (max.) |
Cold start 30A/115VAC 50A/230VAC |
|||
Overload |
Rated output power 110%~150% start over load protection |
|||
Protection mode:AC Charging mode:hiccup mode auto-recovery after fault conditionis remaved |
||||
Battery protection |
9.5~11V 20~22V |
|||
At low voltage |
Protection mode:cuoff output |
|||
Withstand voltage |
IP-O/P:3KVAC I/P-FG:1. 5KVAC O/P-FG:0 5KVAC |
|||
Working temperature |
-10~+60"C, 20%~90%RH |
|||
Safety standards |
Compliance to UL60950-1 |
|||
EMC standards |
Compliance to EN55022,CLASSB |
|||
Dimension |
159x97x38mm |
|||
Packing |
0.56kg/45pcs/26kg/0.041m3/1 .45CUFT |