240W Single Output Industrial DIN Rail Power Supply EDR-240 series
Features:
Universal AC input/ full range
Built-in active PFC function
Protections: Short circuit/ Over load/ Over voltage/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
1 year warranty
SPECIFICATIONS | ||
OUTPUT | ||
Model |
EDR-240-24 |
EDR-240-48 |
DC Voltage |
24V |
48V |
Rated Current |
10A |
5A |
Current Range |
0-10A |
0-5A |
Rated Power |
240W |
240W |
Ripple & Noise |
150mVp-p |
360mVp-p |
Voltage Adj. Range |
21-28V |
43-53V |
Voltage Tolerance |
±1% |
±1% |
Setup, Rise Time | 800ms,40ms/230VAC 800ms,40ms/115VAC at full load | |
Hold Up Time | 24ms/230VAC 24ms/115VAC at full load | |
INPUT | ||
Voltage Range | 176~264VAC 47~63Hz; 240~370VDC | |
AC Current | 2.8A/115V 1.4A/230V | |
Efficiency |
84% |
85% |
Inrush Current | Cold start 27A/115V 45A/230V | |
Leakage Current | <3.5mA/240VAC | |
PROTECTION | ||
Over Load | 105%~150% | |
Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||
Over Voltage |
30-36V |
54-60V |
Protection type: Shut down o/p voltage, re-power on to recover | ||
Over Temp. | 100℃±5℃(TSW1) | |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down | ||
ENVIRONMENT | ||
Working Temp., Humidity | -10℃~+70℃; 20%~90%RH | |
Storage Temp., Humidity | -20℃~+85℃; 10%~95%RH | |
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes | |
SAFETY | ||
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | |
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC | |
STANDARD | ||
Safety Standard | Design refer to UL508,UL60950-1, TUV EN60950-1 | |
EMC Standard | EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2) | |
OTHERS | ||
Dimension | 63*125.2*115mm(L*W*H) | |
Weight | 0.85Kg | |
Packing | 20pcs/17.5Kg/1.2CUFT | |
NOTE | ||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3 .Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5 . Derating may be needed under low input voltages. Please check the derating curve for more details. |