page_banner

Products

15W Single Output Industrial DIN Rail Power Supply DR-15 series

Short Description:

Universal AC input/ full range

Protections: Short circuit/ Over load/ Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5 or 15

Isolation classⅡ

LED indicator for power on

No load power consumption<0.5W

100% full load burn-in test

2 years warranty


Product Detail

Product Tags

Product introduction

Universal Din Rail power supply Dr&MDR series;

Constant Current LED Driver;

Singel output AC to DC,AC 110V  220V and DC 12V, 24V, 48V are common find;

Often used in Industrial Automation, it is more convenient to disassemble, saving time and effort;

The power supply is our hot-selling products with stable quality;Universal AC input/Full range

Installed on DIN rail TS35/7.5 or 15

Protections: Short circuit/Overload/Over voltage

No load power consumption <0.75W

LED indicator for power on

NEC class 2/LPS compliant (selected modeis )

Cooling by free air convection

100% full load burn-in test

2 years warranty

Features

15W Single Output Industrial DIN Rail Power Supply DR-15 series

Universal AC input/ full range

Protections: Short circuit/ Over load/ Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5 or 15

Isolation classⅡ

LED indicator for power on

No load power consumption<0.5W

100% full load burn-in test

2 years warranty 

Specifications

SPECIFICATIONS
OUTPUT  
Model DR-15-5 DR15-12 DR-15-15 DR-15-24
DC Voltage 5V 12V 15V 24V
Rated Current 2.4A 1.25A 1A 0.63A
Current Range 0-2.4A 0-1.25A 0-1A 0-0.63A
Rated Power 12W 15W 15W 15.2W
Ripple & Noise 80mVp-p 120mVp-p 120mVp-p 150mVp-p
Voltage Adj. Range 4.75-5.5V 10.8-13.2V 13.5-16.5V 21.6-26.4V
Voltage Tolerance ±2% ±1% ±1% ±1%
Line regulation ±1% ±1% ±1% ±1%
Load regulation ±1% ±1% ±1% ±1%
Setup, Rise, Hold Up Time 1000ms, 50ms/230VAC 1000ms, 50ms/115VAC at full load  70ms/230VAC          16ms/115VAC at full load
INPUT  
Voltage Range 85 ~ 264VAC          120 ~ 370VDC
AC Current 0.88A/115VAC          0.48A/230VAC
Efficiency 77% 84% 83.50% 85%
Inrush Current COLD START 35A/115VAC          65A/230VAC
PROTECTION  
Over Load  105%~160% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage  5.75-6.75V 13.8-16.2V 17.25-20.25V 27.6-32.4V
Protection type: Shut off o/p voltage, clamping by zener diode
ENVIRONMENT  
Working Temp., Humidity -20℃~+60℃; 20%~90% RH non-condensing
Storage Temp., Humidity -40℃~+85℃; 10%~95%RH
Temp. Coefficient ±0.03%/℃(0~50℃)
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes, Mounting: Compliance to IE60068-2-6
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC
Isolation Resistance I/P-O/P: 100M Ohms / 500VDC/ 25℃/ 70%RH
STANDARD  
Safety Standard Design refer to UL60950-1,TUV EN60950-1,EN50178
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3, heavy industry level, criteria A
OTHERS  
Dimension 25*93*56mm(W*H*D)
Weight 0.1Kg
Packing 140pcs/15KG/0.92CUFT
NOTE  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
DR-15-12) (1)
DR-15-12) (2)
DR-15-12) (3)
DR-15-12) (4)
DR-15-12) (5)
DR-15-12) (6)
DR-15-12) (7)
DR-15-12) (8)
DR-15-12) (9)
DR-15-12) (10)
DR-15-12) (11)
DR-15-12) (12)

  • Previous:
  • Next:

  • Write your message here and send it to us