page_banner

Products

60W Single Output DIN Rail Power Supply MDR-60 series

Short Description:

Universal AC input/ full range

Protections: Short circuit/ Over load/ Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5or 15

isolation classⅡ

LED indicator for power on

100% full load burn-in test

2 years warranty


Product Detail

Product Tags

Proper use of guide rail power supply

1. The AC voltage specification used by the Din Rail power supply is 110VAC 220VAC 380VAC. Before powering on the power supply, check whether the connected voltage matches the power supply input voltage.

2. Do not connect the load before powering on for the first time, first check whether the output voltage of the power supply is consistent with the power supply of the connected equipment, so as not to damage the connected equipment.

3 The ground wire must be connected before the power supply is used. The ground wire of this type of power supply is at the position marked in the figure.

4. The power supply should be placed in a well-ventilated center.

5 The output current of the rail power supply is definitely determined; it is affirmed according to the rated standard current of the equipment supplied by the rail power supply or the uniform current value measured by a multimeter. When the ambient temperature is high, the air activity is not good, and the load is rational, an additional current margin of 20-30% should be prepared.

6 The input power of the rail power supply is determined: the rated input power of the rail power supply depends on the rated power of the supplied equipment. Under the condition of not knowing the rated power of the equipment supplied, it can be obtained based on the product value of the rated current and voltage of the equipment supplied (current X voltage = power). When the user selects the power supply, it should be greater than 15-30% of the practical power and peak power.

7 The number of DC output of the rail power supply is determined: the rail power supply normally has up to four outputs. (S-single group, D-double group, T-three group, Q-four group) According to the equipment provided.

8 The rail power supply has maintenance functions such as over/under voltage, over current, overheating maintenance and fan heat dissipation. Please stop the selection based on the actual application status to strengthen the stability and reliability of the system engineering.

9 The types of rail power supplies are: industrial iron shell type, rail type, LED outdoor rainproof and waterproof type, etc. Please choose according to practical application.

Features

60W Single Output DIN Rail Power Supply MDR-60 series

Universal AC input/ full range

Protections: Short circuit/ Over load/ Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5 or 15

isolation classⅡ 

LED indicator for power on

100% full load burn-in test

2 years warranty 

Specifications

SPECIFICATIONS
OUTPUT  
Model MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
DC Voltage 5V 12V 24V 48V
Rated Current 10A 5A 2.5A 1.25A
Current Range 0-10A 0-5A 0-2.5A 0-1.25A
Rated Power 50W 60W 60W 60W
Ripple & Noise 80mVp-p 120mVp-p 150mVp-p 200mVp-p
Voltage Tolerance ±2% ±1% ±1% ±1%
Line regulation ±1.0% ±1.0% ±1.0% ±1.0%
Load regulation ±1.0% ±1.0% ±1.0% ±1.0%
Setup, Rise Time 500ms,30ms/230VAC   200ms,30ms/115VAC at full load
Hold Up Time 50ms/230VAC   20ms/115VAC at full load
INPUT  
Voltage Range 85~264VAC   47~63Hz; 120~370VDC
AC Current 1.8A/115VAC   1A/ 230VAC
Efficiency 78% 86% 88% 87%
Inrush Current Cold start 30A/115VAC   60A/230VAC
Leakage Current <1mA/240VAC
PROTECTION  
Over Load 105%~150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage 6.25-7.25V 15.6-18V 31.2-36V 57.6-64.8V
Protection type: Shut down o/p voltage, re-power on to recover
ENVIRONMENT  
Working Temp., Humidity -20℃~+70℃; 20%~90% RH non-condensing
Storage Temp., Humidity -40℃~+85℃; 10%~95%RH
Temp. Coefficient ±0.03%/℃(0~50℃)
Vibration 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
SAFETY  
Withstand Voltage I/P-O/P: 3KVAC   I/P-FG:2KVAC   O/P-FG:0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-F/G: >100M Ohms / 500VDC/25℃/70% RH
STANDARD  
Safety Standard Design refer to UL508, UL60950-1,TUV EN60950-1,EN50178
EMC Standard Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2,EN61204-3, heavy industry level, criteria A
OTHERS  
Dimension 40*90*100mm(W*H*D)
Weight 0.33Kg
Packing 42pcs/carton/14.8kg/0.82CUFT
NOTE  
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

 

MDR-60-24 (1)
MDR-60-24 (2)
MDR-60-24 (3)
MDR-60-24 (4)
MDR-60-24 (5)
MDR-60-24 (6)
MDR-60-24 (7)
MDR-60-24 (8)
MDR-60-24 (9)
MDR-60-24 (10)
MDR-60-24 (11)
MDR-60-24 (12)

  • Previous:
  • Next:

  • Write your message here and send it to us